3.2 Front Panel LED Indications

Indicator
Block 1
FIRE
FAULT
Test
Disablement
Delayed Mode
Alarms Silenced
Buzzer Muted
Sounders Disabled
Relays Disabled
Fire Routing
Equipment
Power
Block 2
Function 1
Supply Fault
System / CPU Fault
Sounder Fault
Earth Fault
Function 2
Block 3
Zone FIRE
Page 8
Colour
Function
Red
The panel has detected a fire alarm
condition, or the 'Sound Alarms' key
has been pressed.
Yellow
The panel has detected a fault.
Yellow
The system is in test mode. The LCD
shows which zones are being tested.
Yellow
Part of the system, either input or
output, has been disabled manually
by the user.
Yellow
This indicates that the system is operating
with delays to the sounder outputs and the
delays are active (in force).
Yellow
The sounder outputs have been
silenced.
Yellow
A fault or alarm has been
acknowledged and the internal
buzzer silenced.
Yellow
The sounder outputs have been
disabled.
Yellow
The relay outputs have been
disabled.
Red
Indicates the output to fire routing
equipment (i.e. Fire Brigade) is
activated. NOT CURRENTLY USED.
Green
STEADY: Indicates presence of power
(either AC Mains and / or batteries).
Yellow
Function programmed when
commissioned – refer to site notes.
Yellow
There is a problem with the power
supply, battery or supply input.
Yellow
The CPU has reset or a system fault
has occurred.
Yellow
This indicates a wiring fault with one
of the sounder output circuits.
Yellow
An earth connection fault has
occurred on a cable.
Yellow
Function programmed when
commissioned – refer to site notes.
Red
STEADY: The zone is in a fire alarm
condition.
Table 3 - LED Functions
Document No. 996-148-000-5, Revision: 5
Dimension Series
How to Clear
Correct the condition causing the alarm
and then perform a panel reset.
Correct the condition causing the fault
and then perform a panel reset.
Cancel / Stop test when finished.
Re-enable the device or devices. Refer
to Disablement Function.
The delays may be enabled or disabled.
Refer to Disablement Function.
Correct the alarm condition and then
perform a panel reset. NOTE: Press
SILENCE / RESOUND again to
reactivate the sounders.
NOTE: the sounders will automatically
resound if a new alarm occurs in any
zone, unless this function has been
disabled during panel commissioning.
Correct the condition causing alarm or
fault and then perform a manual reset.
NOTE: If an new alarm occurs in any
zone or a fault occurs, the internal
buzzer automatically resounds.
Refer to Disablement Function.
Refer to Disablement Function.
Correct the fault condition and then
perform a panel reset.
Correct the problem, if appropriate, and
then perform a panel reset.
Correct the fault condition and then
perform a panel reset.
Correct the fault condition and then
perform a panel reset.
Correct the alarm condition and then
perform a panel reset.