15.6.4.2 Mapping – Measured Values 1 – 15
Parameter
Name
Unit
Note on frequency measured
values:
If a frequency measured value
(unit: Hz) has been parameterized
without a multiplier (multiplier: -), an
additional check is made whether
the resulting value is in the range of
15 Hz to 65 Hz. Measured values
outside this range are marked as in-
valid.
Note on factors:
Selecting a multipier for the follow-
ing units is not recommended and
will be rejected: -none-
°
°C
°F
%
Register type
Data format on bus
(See following table.)
Register number
Scaling factor
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
Default Setting
MV x Slv 1
(x = 1 to 15)
Multiplier: -
Unit: -none-
-none-
Float32 (2 registers)
1
1.000
15 Operating Parameters
15.6 Administrative
Setting Range
Max. 31 characters
Max. 10 characters if the name is also to
be displayed on the device display.
m (milli)
c (centi)
d (deci)
-
h (hecto)
k (kilo)
M (Mega)
G (Giga)
-none-
m
kg
s
A
°C
V
Hz
W
Pa
2
m
3
m
VA
var
°
Wh
VAh
varh
%
°F
-none-
Input registers
Holding registers
For -none-, the assignment is ignored
and the corresponding measured value
cannot be selected for other functions.
Float32 (2 registers)
Int16 (1 register)
Int16_Ung8000h (1 register)
UInt16 (1 register)
UInt32 (2 registers)
1 to 65 535
Any float value
0.00: resulting measured value = 0.00
363