15 Operating Parameters
15.6 Administrative
15.6.4
Modbus Slave Devices 1 – 8
15.6.4.1 Basic Settings
Parameter
Name
Activated
Device address / Unit ID
(Modbus slave device address)
Response timeout
Retry limit
Scan cycle for measured values
Scan cycle for indications
Scan cycle on error
362
Default Setting
Modbus slave device 1
no
1
10 (*10 ms)
2
50 (*10 ms)
0 (*10 ms)
5 s
Setting Range
Max. 31 characters
no
yes (= Activation of the option field):
The buttons for parameterization of the
mapping data are also activated for the
slave device here.
1 to 247
Address corresponds to the Unit ID in
the Modbus TCP telegram with simulta-
neous use of the Modbus Gateway func-
tion.
1 to 6000 * 10 ms
(10 ms to 60 s)
0 to 10
(0 = no request retries)
Number of request retries after expira-
tion of Response timeout before a com-
munication error for the Modbus slave is
identified.
0 to 36 0000 * 10 ms
(10 ms to 1 h)
0 = each request cycle
Minimum time difference between the
measured-value requests.
0 to 36 0000 * 10 ms
(10 ms to 1 h)
0 = each request cycle
Minimum time difference between the
measured-value requests.
1 to 3600 s
( 1 s to 1 h)
Retry cycle for sending request tele-
grams if the retry limits are exceeded or
in the case of error responses.
SICAM Q100, 7KG95xx, Device Manual