Methods of Load-Profile Determination

NOTE
The parameterization of the load profile is described in detail in chapter 8.3.5.1. Note the information specified
there.
SICAM Q100 supports the following load-profile determination methods:
Fixed Block
Rolling Block
Fixed Block method
The Fixed Block method with a measuring-period length of 15 minutes is the default setting. In addition, the
number of subperiods of this method is set to 1. The load-profile data are determined at the end of every
measuring period and stored in the ring buffer and transmitted, if necessary, or displayed on the user interface.
Measuring
period
3
Time of the recording of
the load profile data of the
ended measuring period
2
1
0
Figure 5-2
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
Duration of a
measuring period
15
Determination of the load profile according to the Fixed Block method
30
45
5 Energy Management
5.1 Load-Profile Determination
t [min]