8.3.6.6 Report Configuration
The Report configuration allows you to parameterize the PQ threshold parameters (User defined). You can
adjust the process connections to the installation environment and enter different operational settings.
Alternatively, you can use the default values according to EN 50160 LV&MV or EN 50160 HV.
Default Settings and Setting Ranges
Table 8-18
Company:
Department:
Supervisor:
Inspector:
Location:
Comment:
Evaluation mode according to:
Flagging acc. to
IEC 61000-4-30
Power frequency
99.5 % of measurement should be in -1.0 % to 1.0 % deviation of the
power frequency.
100 % of measurement should be in -6.0 % to 4.0 % deviation of the
power frequency.
Power supply voltage magnitude
95 % of measurement should be in -10.0 % to 10.0 % deviation of the
nominal/declared supply voltage.
100 % of measurement should be in -15.0 % to 10.0 % deviation of
the nominal/declared supply voltage.
Flicker severity
95 % of measurement should be less than 1.0
Voltage unbalance
95 % of measurement should be less than 2.0 %.
100 % of measurement should be less than 3.0 %.
Subgroup Total Harmonic Distortion factor (THDS)
95 % of measurement should be less than 8.0 %.
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
Report Configuration
Parameter
EN 50160 LV&MV
no
1)
Default Setting
General Information
-
Power Quality Report
8 Operation at Use of a PC
8.3 Configuration of the Device
Setting Range
Any text displayed in the
printout of the power quality
report
EN 50160 LV&MV
EN 50160 HV
User defined
no
yes
Any setting for user-defined
evaluation mode
Any setting for user-defined
evaluation mode
Any setting for user-defined
evaluation mode
Any setting in % for user-
defined evaluation mode
179