Parameterizing a Limit
To change, for example, limit 1, proceed as follows:
✧
In the navigation window, select the Operational parameters menu, then the Select automation
functions submenu and click Limits 1-8.
Figure 8-34
✧
Enter the desired values in the fields and select the parameters in the list boxes and option fields as
described in Table 8-6.
Hysteresis of the Limit Value Violation
100 %
Limit Max
Limit Min
0 %
Figure 8-35
NOTE
Select Measurement -none- to disable the corresponding limit indication.
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
Configure Tab, Limits 1-8 Input/Output Window (Detail)
Permissible
Start
End
Start
Hysteresis (General Representation)
Hysteresis range
range
t
End
8 Operation at Use of a PC
8.3 Configuration of the Device
153