8 Operation at Use of a PC
8.3 Configuration of the Device
Description and setting ranges of the parameters in the text file:
Table 8-29
Label
Quantity (MV)
MT
MV
DS
MV, I
RN
MV, I
RT
MV, I
OF
I
FM
MV, I
SC
MV
UN
MV
208
Description and setting ranges of the parameters in the text file.
Measured
Indication (I)
Mapping Type
(Data type)
Description
Name of the associated data object
Register number
(within the selected register type
RT)
Register type
Bit offset
(for INDICATION in Holding regi-
sters)
Data format
Scaling factor for MEASURAND
Unit-multiplier for MEASURAND
Description
Setting Range
MEASURAND
INDICATION
String with max. 31 characters
Longer strings are cut at 31 charac-
ters during import.
1 to 65 535
0x0 – Coil status register
0x1 – Input status register
0x3 – Input register
0x4 – Holding register
0 to 15 (for FT = 1BIT)
0 to 31 (for FM = 1BITINUINT32)
For MEASURAND:
FLT32, INT16, UINT16, UINT32,
INT16INV7FFF and INT16INV8000
For INDICATION:
1BIT, 1BITINUINT32
Arbitrary float value
1: dimensionless
2: Meter
3: kg
4: s
5: A
23: °C
29: V
33: Hz
38: W
39: Pa
2
41: m
3
42: m
61: VA
63: var
64: °
71: VAh
72: Wh
73: varh
75: %
76: °F
SICAM Q100, 7KG95xx, Device Manual