8 Operation at Use of a PC
8.3 Configuration of the Device
8.3.7.2.2
Parameterizing the Ethernet Communication with IEC 61850 Bus Protocol
In the Bus protocol list box select the entry IEC 61850.
The Communication Ethernet input/output window with Protocol IEC 61850 opens.
Figure 8-58
Enter the desired values into the fields and select the parameter in the list boxes as described in
Table 8-22.
If several SICAM Q100 devices are used in the substation, change the name of the SICAM Q100 (factory
setting SICAM_Q100_01) in the IED Name field.
The name must be identical to the name which has been parameterized for this SICAM Q100 in the
configurator of the substation.
After the parameterization click Send.
After clicking Send, the parameters are transmitted to the device but not enabled yet (passive set of
parameters).
192
Configure Tab, Communication Ethernet via IEC 61850 Input/Output Window
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018