Siemens SICAM Q100 Device Manual page 152

Power monitoring device and class a power quality recorder
Hide thumbs Also See for SICAM Q100:
Table of Contents

Advertisement

8 Operation at Use of a PC
8.3 Configuration of the Device
8.3.3.2 Automation Functions
8.3.3.2.1
Limit Settings
In the Select automation functions menu you can set upper or lower limits for up to 16 measured values. Limit
violations of the upper or lower value range can be output as indications. Limiting value violations can be
signaled at the device via the 2 binary outputs and the LEDs H1 and H2. Furthermore, all 16 limit violations can
be sent to peripheral devices via the communication interfaces.
The programmable limits are divided into two groups Limits 1-8 and Limits 9-16. The parameterization is
identical for all limits.
Default Settings and Setting Ranges of the Limits
Table 8-6
Parameter
Measurement
Limit
Limit type
Hysteresis (%)
Violation indication
1)
31 bytes of UTF-8
152
Limit Settings
Default Setting
-none-
0.0
Lower
1.0
Limit Violation x
(x = 1 to 16)
Setting Range
Acc. to list box
(see chapter 15)
-1 000 000 000 to 1 000 000 000 (unit)
Lower
Upper
0.0 to 10.0
Any
1)
Max. 31 characters
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018

Advertisement

Table of Contents
loading

This manual is also suitable for:

7kg95 series

Table of Contents