On the Configure tab, Memory management menu item (see chapter 8.4.2.6) allocate 50 % of the
storage capacity to the Measurement recorder and activate the ring buffer function.
Figure 8-123
✧
Confirm the factory-set report configuration (see chapter 8.3.6.6).
✧
On the Configure tab, Recording control menu item (see chapter 8.3.6.7) select Start immediately.
Figure 8-124
✧
Go to the Configure tab, Save configuration to file menu item to save your device configuration as the
active parameter set as described in Save Configuration to File.
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
Configure Tab, Memory Management Example
Configure Tab, Start Immediately Example
8.7 Example of a Parameterization and Measured Value Evaluation
8 Operation at Use of a PC