8 Operation at Use of a PC
8.3 Configuration of the Device
8.3.3.1 Process Connections
8.3.3.1.1
AC Measurement
Default Settings and Setting Ranges of Measured-Value Acquisition
NOTE
Pay careful attention to the values you configure to ensure that they do not contradict each other.
Table 8-2
Settings for Measured-Value Acquisition
Parameter
Rated frequency
Network type
Power quality values for
Calculate Voltage RMS values
2)
PN and PP
Nominal/Declared supply
1)
voltage
Voltage transformer
Primary rated voltage
Secondary rated voltage
Current transformer
Primary rated current
Secondary rated current
Transformer ratio In
Primary rated current In
Zero-point suppression
Voltage harmonic unit
Measurement aggregation
1)
In the case of contradictory parameter settings, Primary nominal voltage is indicated as faulty (red) and
Network type as not adjustable (gray). Moreover, the Send button is disabled.
2)
Power quality values for and Calculate Voltage RMS values PN and PP are available only if the
following Network type is selected: Four-wire, three phase, unbalanced.
3)
Transformer ratio In is available only if the following Network type is selected: Four-wire, three phase,
unbalanced.
140
50 Hz
1)
Four-wire,
three phase, unbalanced
2)
Phase to neutral
no
AC 230.00 V
no
AC 10 000.00 V
AC 100.00 V
no
AC 1 000.00 A
AC 1.00 A
3)
no
AC 1 000.00 A
4)
0.3 % (from Unom, Irated)
%
5)
-none-
Default Setting
Setting Range
Setting 50 Hz: 50 Hz ±7.5 Hz
Setting 60 Hz: 60 Hz ±9 Hz
Acc. to list box
(see chapter 15)
Phase to neutral
Phase to phase
no
yes
AC 57.73 V to 400 V (autorange)
IEC 61000-4-30 Class A: to
AC 230 V: 200 % overvoltage
> AC 230 V to 400 V: 200 % to
15 % overvoltage
UL conditions:
to AC 170 V: 200 % overvoltage
> AC 170 V to 300 V: 200 % to
15 % overvoltage
no
yes
AC 100.00 V to 1 000 000.00 V
AC 1.00 V to 460.00 V
no
yes
AC 1.00 A to 100 000.00 A
AC 1.0 A to 10.0 A
no
yes
AC 1.0 A to 100 000.0 A
0.0 % to 10.0 %
%
V
-none-
150/180-cycle interval
SICAM Q100, 7KG95xx, Device Manual