2 Overview

2.1 Device Versions

2.1
Device Versions
SICAM Q100 is a multifunctional device for the detection, calculation, recording, evaluation, display, and trans-
mission of measured electrical quantities with the following properties:
Consistent Device Properties
All devices consistently feature the following properties:
Device type:
Power Monitoring Device and Class A Power Quality Recorder with measured value recorders and
internal 2 GB memory
Panel flush mounting device with display for measured values and parameterization
Plastic case 96 mm x 96 mm x 100 mm (W x H x D)
Web server for parameterization, visualization, and data management
Galvanically isolated voltage measuring inputs
Transmitting measured values using communication protocols
Input and output circuits:
4 inputs for alternating voltage measurements
4 inputs for alternating current measurements
2 binary inputs for example, for synchronization pulses of the load profile or external triggers
2 binary outputs
Measurement acc. to standard IEC 61000-4-30, class A
Measured quantities
Voltage V
Current I
System frequency f (fundamental)
Active power P (accuracy class 0.2S; ANSI C12.20 current class 2 and current class 10)
Reactive power Q
Apparent power S
Energy measurements W
Active power factor cos 
Measurement up to the 63th harmonics/49th interharmonics of voltage and current
Flicker acc. to IEC 61000-4-15
Mains signalling voltage
Harmonics phase angles, harmonic power
Measurements for evaluation and supervision
Minimum/mean/maximum values
Event detection, for example voltage dips, voltage swells, voltage interruptions
Limit violations
Energy management (load profiles and tariffs)
Transient detection
Data export
CSV data
PQDIF data
IEEE1159.3: PQDIF for PQ records (events, measurements, records)
COMTRADE data
IEC 60255-24/IEEE Std C37.111: Measuring relays and protection equipment – Part 24: Common
format for transient data exchange (COMTRADE for power systems) for fault records