8 Operation at Use of a PC
8.3 Configuration of the Device
Parameterizing an Indication
Select the desired parameters for an indication in the list boxes and option fields (see Figure 8-27,
example terminal G1/G2) as described in Table 8-4.
NOTE
If you select -not assigned- as the source of an indication and/or energy counter, the corresponding binary
output is inactive.
You can select the following output types in the Operating mode list box:
Persistent: The binary output has the status ON or OFF. If the indication becomes invalid, the binary
output continues to maintain its current status.
Indication
Binary output
not inverted
Binary output
inverted
Figure 8-28 Persistent
Persistent with fail save: If the indication becomes invalid, the binary output switches into the OFF
state, that is if Source inverted = no, or it switches into the ON state if Source inverted = yes.
Indication
Binary output
not inverted
Binary output
inverted
Figure 8-29 Persistent with Fail Save
Pulse without retrigger: This indication is output as pulse. If the indication changes again while the
output pulse is ON, the pulse output time is not restarted. This means that a change of the indication
during the pulse output will be ignored.
Indication
Binary output with
Source inverted = no
Binary output with
Source inverted = yes
Figure 8-30 Pulse without Retrigger
148
Indication
ON
invalid
OFF
Output
ON
OFF
ON
Output
OFF
Indication
ON
OFF
Output
ON
OFF
ON
Output
OFF
Indication
Indication
ON
OFF
Output
Output
ON
OFF
Output time
Output
ON
OFF
Output time
invalid
invalid
invalid
Indication
Output
Output
Output
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018