8 Operation at Use of a PC
8.3 Configuration of the Device
Settings Protocol Modbus
Enter the desired values in the fields and select the parameters in the list boxes and in the option field as
described in Table 8-22.
NOTE
If you have selected no under Use a user-port number, you can adjust only the Access rights for user
port 502, the Keep Alive time and the Communication supervision time parameters.
Figure 8-55
Settings Modbus TCP/RTU Gateway
NOTE
The Modbus TCP/RTU Gateway function requires that the Modbus RTU Master has been selected as serial
protocol in addition; see chapter 8.3.7.3.
Activate Modbus TCP/RTU Gateway as follows: Menu Administrative  Communication Ethernet 
Modbus TCP/RTU Gateway  Activated  yes.
Figure 8-56
Enter the desired values into the fields (acc. to Table 8-22).
After the parameterization click Send.
After clicking Send, the parameters are transmitted to the device but not enabled yet (passive set of
parameters).
190
Protocol Modbus
Modbus TCP/RTU Gateway
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018