Power quality values for and Calculate Voltage RMS values PN and PP are available only under Net-
work type is selected as Four-wire, three phase, unbalanced.
2)
Transformer ratio In is available only if the following Network type is selected: Four-wire, three phase,
unbalanced.
15.1.2

Binary Inputs U1/U2 and U3/U2

Threshold voltage
(one setting for both binary inputs)
Terminals U1/2
1)
Routed as:
Software filter time
(only settable if Routed as: Status information
has been set)
Source inverted
Add entry to operational log
(only settable if Routed as: Status information
has been set)
Binary input indication
Terminals U3/2
1)
Routed as:
Software filter time
(only settable if Routed as: Status information
has been set)
Source inverted
Add entry to operational log
(only settable if Routed as: Status information
has been set)
Binary input indication
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
Parameter
Default Settings
Threshold voltage
19 V
Binary inputs
Status information
1 (* 2 ms)
no
yes
Binary Input 1
Status information
1 (* 2 ms)
no
yes
Binary Input 2
15 Operating Parameters
15.1 Process Connections
Setting Range
19 V
88 V
176 V
Status information
Load profile source
Tariff source
2 ms to 120 000 ms
(settable in 2-ms increments)
no
yes
no
yes
Any
2)
Max. 31 characters
Status information
Load profile source
Tariff source
2 ms to 120 000 ms
(settable in 2-ms increments)
no
yes
no
yes
Any
2)
Max. 31 characters