Siemens SICAM Q100 Device Manual page 131

Power monitoring device and class a power quality recorder
Hide thumbs Also See for SICAM Q100:
Table of Contents

Advertisement

NOTE
If you have selected Get device configuration, an editable copy of the active parameter set of the device is
displayed on the screen. In the meantime, the active parameter set in the device continues to operate.
If you have selected Open configuration from file, you can open and enable or edit the copy of a parameter
set that was already created and saved to a folder.
8.3.1.1 Get Device Configuration
If you have selected Get device configuration in the Configure tab, you can open and edit either the Get
active configuration or the Get default configuration in the input/output window. Proceed as follows:
Figure 8-16
Get Active Configuration and Editing
Click Get active configuration.
A copy of the active set of parameters (= passive set of parameters) of the device is opened for editing.
Check and, if necessary, change the set parameters by opening the desired menus in the navigation
window:
Operational parameters menu according to chapter 8.3.3
HMI settings according to chapter 8.3.4
Recording and reporting according to chapter 8.3.6
Administrative menu according to chapter 8.3.7.
Activate the modified configuration as described in chapter 8.3.1.3.
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
Configure Tab, Get Device Configuration
8 Operation at Use of a PC
8.3 Configuration of the Device
131