General Device Data; Power Supply - Siemens SICAM Q100 Device Manual

Power monitoring device and class a power quality recorder
Hide thumbs Also See for SICAM Q100:
Table of Contents

Advertisement

13 Technical Data

13.1 General Device Data

13.1
General Device Data
13.1.1

Power Supply

Direct Voltage
Rated input voltages
Admissible input voltage tolerance
Permitted ripple of the input voltage
Maximum inrush current
At  110 V
At 220 V to 300 V
Maximum power consumption
Alternating Voltage
Rated input voltages
System frequency at AC
Admissible input voltage tolerance
Permitted harmonics
Maximum inrush current
At  115 V
At 230 V
Maximum power consumption
320
24 V to 250 V
±20 %
15 %
< 15 A
 22 A; after 250 µs: < 5 A
6 W
110 V to 230 V
50 Hz/60 Hz
±20 %
2 kHz
< 15 A
 22 A; after 250 µs: < 5 A
16 VA
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018