Siemens SICAM Q100 Device Manual page 322

Power monitoring device and class a power quality recorder
Hide thumbs Also See for SICAM Q100:
Table of Contents

Advertisement

13 Technical Data
13.1 General Device Data
Inputs for Alternating Current Measurements, Connector Block E - Cat III
Input alternating currents
Rated input current range
Max. input current
Power consumption per input
at 5 A
Further information about the current measuring inputs
Max. rated input voltage
Measuring error under environmental influences:
see technical data
Thermal stability
Sampling rate
Binary Inputs, Connector Block U - Cat III
Maximum input voltage
Static input current
UIL min (at threshold voltage 19 V)
UIL max (at threshold voltage 19 V)
UIL min (at threshold voltage 88 V)
UIL max (at threshold voltage 88 V)
UIL min (at threshold voltage 176 V)
UIL max (at threshold voltage 176 V)
Progagation delay low to high
Binary Outputs, Connector Block G - Cat III
Maximum contact voltage
Alternating voltage
Direct voltage
Maximum currents
Maximum continuous contact current
Maximum pulse current for 0.1 s
Further information about the binary outputs
Internal impedance
Admissible switching frequency
322
AC 1 A to 5 A (autorange)
AC 10 A
100 mVA
150 V
acc. to IEC 61000-4-30 Ed. 3 Class A (0.1 %)
10 A continuous
100 A for max. 1 s
10.24 kHz
DC 300 V
1.34 mA ± 20 %
DC 14 V
DC 19 V
DC 66 V
DC 88 V
DC 132 V
DC 176 V
2.8 ms ± 0.3 ms
230 V
250 V
100 mA
300 mA
50
10 Hz
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018

Advertisement

Table of Contents
loading

This manual is also suitable for:

7kg95 series

Table of Contents