Siemens SICAM Q100 Device Manual page 180

Power monitoring device and class a power quality recorder
Hide thumbs Also See for SICAM Q100:
Table of Contents

Advertisement

8 Operation at Use of a PC
8.3 Configuration of the Device
Table 8-18
Voltage event interruptions
1. Short interruption until 1 second duration
2. Short interruption until 3 minute duration
3. Long interruption longer than 3 minute duration
Harmonic voltages
Even harmonics
Odd harmonics: multiples of 3
Odd harmonics: not multiples of 3
Mains signalling voltages
Supply voltage should be in -15.0 % to +15.0 % deviation of the
nominal/declared supply voltage
99.0 % of "YYY" Hz mains signalling voltage should be less than "xxx"
% of the nominal/declared supply voltage
1)
According to EN 50160, up to 3 % unbalance can occur in 3-wire networks in areas with many 1-wire and
2-wire connections.
2)
The frequency "YYY" and limit "xxx" are based on the configured frequency.
NOTE
The factory settings are based on EN 50160. If you have changed the settings, the set parameters are applied
after a device restart. Resetting to the factory settings is possible.
180
Report Configuration (cont.)
2)
Any setting for user-defined
evaluation mode
Any setting for user-defined
evaluation mode
Any setting for user-defined
evaluation mode
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018

Advertisement

Table of Contents
loading

This manual is also suitable for:

7kg95 series

Table of Contents