15 Operating Parameters
15.5 Recording and Reporting
Supply voltage interruptions:
1. Short interruption until 1 second duration
2. Short interruption until 3 minute duration
3. Long interruption longer than 3 minute duration
Harmonic voltages:
Even harmonics
Odd harmonics: multiples of 3
Odd harmonics: not multiples of 3
Mains signalling voltages
Supply voltage should be in -15.0 % to +15.0 % deviation of the nominal/
declared supply voltage
99.0 % of "YYY" Hz mains signalling voltage should be less than "xxx" % of
the nominal/declared supply voltage
1)
According to EN 50160, up to 3 % unbalance can occur in 3-wire networks in areas with many 1-wire and
2-wire connections.
2)
The frequency "YYY" and limit "xxx" are based on the configured frequency.
15.5.7

Recording Control

Parameter
Start record option
Start time
Recording status
15.5.8

Transient Detection

Parameter
Transient reference level
356
2)
Default Setting
Start next 10th minute
-
-
Default Setting
110 %
Any setting for user-defined
evaluation mode
Any setting for user-defined
evaluation mode
Any setting for user-defined
evaluation mode
Setting Range
Start next minute
Start next 10th minute
Start immediately
Start next hour
Start next day
Display of the start time in:
Depends on the configuration of Date/time
format.
Not settable
Status display of recorder started or recorder
stopped
Setting Range
110 % to 240 % of Primary nominal voltage
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018