Siemens SICAM Q100 Device Manual page 361

Power monitoring device and class a power quality recorder
Hide thumbs Also See for SICAM Q100:
Table of Contents

Advertisement

Parameter
Additional inter-character timeout
Maximum 0x/1x register gap
Maximum 3x/4x register gap
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
Default Setting
1 ms
40
10
15 Operating Parameters
15.6 Administrative
Setting Range
0 ms to 100 ms
The Modbus specification requires that
the individual characters of a serial
Modbus RTU telegram have to be
transmitted successively with a maxi-
mum character gap of 1.5 character
times (or max. 750 µs for Baud rates
>19 200 bit/s). Longer silent intervals
between the characters are interpreted
as telegram end.
A longer gap between the characters
can be tolerated with this parameter.
Note that this also causes longer cycle
times then.
If at least one SICAM P50 device is
connected to the bus, at least the fol-
lowing values have to be set for Addi-
tional inter-character timeout:
1200 bit/s, 2400 bit/s: 0
4800 bit/s, 9600 bit/s: 2
19 200 bit/s: 3
38 400 bit/s: 4
57 600 bit/s, 115 200 bit/s: 6
0 to 200
Maximum number of not-mapped reg-
isters which are being requested
between mapped registers in one
request telegram.