8 Operation at Use of a PC
8.3 Configuration of the Device
Table 8-21
Error indication after
Additional Parameter if the Source is Fieldbus (Modbus RTU and IEC 60870-5-103)
Error indication after
Parameterizing the Time Synchronization
To change the time synchronization, proceed as follows:
In the navigation window, select the Administrative menu and click Time synchronization.
Figure 8-53
Enter the desired values in the fields and select the parameters in the list boxes and in the option field as
described in Table 8-21.
After the parameterization click Send.
The parameters are transmitted to the device but not enabled yet (passive set of parameters).
If you do not want to make any additional settings, continue with the Activation of the device configuration
according to section Activating the Set of Parameters. If you want to change other settings, enter the
changes and then enable the device configuration as described in section Activating the Set of
Parameters.
186
Time Synchronization Settings (cont.)
Parameter
Configure Tab, Time Synchronization Input/Output Window, Ethernet NTP Selected
Default Setting
10 min
10 min
Setting Range
2 min to 120 min
2 min to 120 min
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018