Environmental Conditions And Climatic Stress Tests - Siemens SICAM Q100 Device Manual

Power monitoring device and class a power quality recorder
Hide thumbs Also See for SICAM Q100:
Table of Contents

Advertisement

13.1.4

Environmental Conditions and Climatic Stress Tests

Environmental Conditions
Temperature data
Air humidity data
Altitude and operation
site
Climatic Stress Tests
Standards: IEC 60068
Dry cold:
IEC 60068-2-1 test Ad
Dry heat during operation, storage, and transport:
IEC 60068-2-2 test Bd
Damp heat:
IEC 60068-2-78 test Ca
Change of temperature:
IEC 60068-2-14 test Na and Nb
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
Operating temperature
Devices with display: the legibility of the display is
impaired at temperatures < 0 °C (+32 °F).
Temperature during transport
Temperature during storage
Maximum temperature gradient
Mean relative humidity per year
Maximum relative humidity
Condensation during operation
Condensation during transport and storage
Max. altitude above sea level
Operation site
13 Technical Data
13.1 General Device Data
-25 °C to +55 °C
-13 °F to +131 °F
-40 °C to +70 °C
-40 °F to +158 °F
-40 °C to +70 °C
-40 °F to +158 °F
20 K/h
 75 %
95 % 30 days a year
Not permitted
Permitted
2000 m
Only indoors
325