Tap Settings

The MDXII is equipped with six internal voltage taps so that six different output ranges can be
selected for each master/slave system. Each MDXII leaves the factory set at tap 4, but you can
easily select a different tap from any of the three interfaces.
The following table indicates the maximum current that can be produced at each tap. It also
shows the range of output voltages available at each tap when the MDX is in voltage
regulation.

Table B-11. Output Parameters

Max.
Power
Tap 1
(kW)
400 V
15
48.0
30
96.0
45
144.0
60
192.0
75
240.0
90
288.0
115
336.0
120
384.0

Selecting the Correct Tap

See the "Operation Overview"chapter for a detailed description of how to select the correct
tap.
5700262-R
Maximum Current for Each Tap
Tap 2
Tap 3
500 V
625 V
37.5
30.0
75.0
60.0
112.5
90.0
150.0
120.0
187.5
150.0
225.0
180.0
262.5
210.0
300.0
240.0
MDXII Power Supplies
Tap 4
Tap 5
800 V
1000 V
24.0
18.75
48.0
37.5
72.0
56.3
96.0
75.0
120.0
93.8
144.0
112.5
168.0
131.3
192.0
150.0
Tap 6
1250 V
15.0
30.0
45.0
60.0
75.0
90.0
105.0
120.0
B-19