WAGO -I/O-SYSTEM 750 Technical Description, Installation And Configuration page 19

Profinet io modular i/o-system fieldbus coupler
Hide thumbs Also See for WAGO-I/O-SYSTEM 750:
Table of Contents

Advertisement

For Products of the WAGO-I/O-SYSTEM 750 with ship specific approvals,
supplementary guidelines are valid:
Electromagnetic compatibility
Immunity to interference acc. to Germanischer Lloyd (2003)
Test specification
IEC 61000-4-2 ESD
IEC 61000-4-3
electromagnetic fields
IEC 61000-4-4 burst
IEC 61000-4-5 surge
IEC 61000-4-6
RF disturances
Type test AF disturbances
(harmonic waves)
Type test high voltage
Emission of interference acc. to Germanischer Lloyd (2003)
Test specification
Type test
(EMC1, conducted)
allows for ship bridge control
applications
Type test
(EMC1, radiated)
allows for ship bridge control
applications
Mechanical strength acc. to Germanischer Lloyd (2003)
Test specification
IEC 60068-2-6 vibration
(category A – D)
WAGO-I/O-SYSTEM 750
PROFINET IO
Technical Condition of the Devices
Test values
6 kV/8 kV (contact/air)
10 V/m 80 MHz ... 2 GHz
1 kV/2 kV (data/supply)
AC/DC
0.5 kV (line/line)
Supply:
1 kV (line/earth)
10 V/m 80 % AM (0.15 ... 80
MHz)
3 V, 2 W
755 V DC
1500 V AC
Limit values
96 ... 50 dB (µV)
60 ... 50 dB (µV)
50 dB (µV)
80 ... 52 dB (µV/m)
52 ... 34 dB (µV/m)
54 dB (µV/m)
außer für: 24 dB (µV/m)
Frequency range
2 Hz ≤ f < 25 Hz
25 Hz ≤ f < 100 Hz
Note on vibration test:
a) Frequency change: max. 1 octave/minute
b) Vibration direction: 3 axes
Technical Data
Strength
Evaluation
class
criteria
3/3
B
3
A
2/3
A
1
A
2
3
A
-
A
-
-
Frequency range
10 kHz ... 150 kHz
150 kHz ... 350 kHz
350 kHz ... 30 MHz
150 kHz ... 300 kHz
300 kHz ... 30 MHz
30 MHz ... 2 GHz
156 MHz ... 165 MHz 3 m
Limit value
± 1.6 mm amplitude (permanent)
4 g (permanent)
• 11
Distance
3 m
3 m
3 m

Hide quick links:

Advertisement

Table of Contents