WAGO -I/O-SYSTEM 750 Technical Description, Installation And Configuration page 35

Profinet io modular i/o-system fieldbus coupler
Hide thumbs Also See for WAGO-I/O-SYSTEM 750:
Table of Contents

Advertisement

Recommendation
With the WAGO ProServe® Software smartDESIGNER, the assembly of a
fieldbus node can be configured. The configuration can be tested via the
integrated accuracy check.
The maximum input current of the 24 V system supply is 500 mA. The exact
electrical consumption (I
Coupler/Controller
I(5 V)
750-613
I(5 V)
Input current I(24 V) =
Note
If the electrical consumption of the power supply point for the 24 V-system
supply exceeds 500 mA, then the cause may be an improperly aligned node
or a defect.
During the test, all outputs, in particular those of the relay modules, must be
active.
WAGO-I/O-SYSTEM 750
PROFINET IO
(24 V)
=
Sum of all the internal current consumption of the connected
total
bus modules
+ internal current consumption coupler/controller
=
Sum of all the internal current consumption of the connected
total
bus modules
5 V / 24 V * I(5 V)
η = 0.87 (at nominal load)
) can be determined with the following formulas:
/ η
total
Power Supply
• 27
System Supply