WAGO -I/O-SYSTEM 750 Technical Description, Installation And Configuration page 177

Profinet io modular i/o-system fieldbus coupler
Hide thumbs Also See for WAGO-I/O-SYSTEM 750:
Table of Contents

Advertisement

Parameter
Substitute value behavior of the
outputs
Substitute output status channel
x
(x = 0.1)
WAGO-I/O-SYSTEM 750
PROFINET IO
Configuration and Parameter Setting of the Modules
Value
according to the device settings*)
Outputs are set to 0
Outputs maintain the last valid
value
Outputs take on their substitute
value
*)
0
1
*) Default settings
I/O Modules
Significance
Applies when the I/O controller does not supply
valid output data for the module or the group of
modules
the set strategy on the side of the station
substitute applies (I/O device).
all outputs are immediately reset
all outputs maintain the last valid value
all outputs switch to their configured substitute
value
When configuring the substitute value behavior on
the side of the I/O module, these values are
transmitted to the binary signal channel with invalid
output states of the I/O controller.