WAGO -I/O-SYSTEM 750 Technical Description, Installation And Configuration page 193

Profinet io modular i/o-system fieldbus coupler
Hide thumbs Also See for WAGO-I/O-SYSTEM 750:
Table of Contents

Advertisement

Parameter
Asynchronous diagnostics
message
Channel x (x = 0 ... 7)
Substitute value behavior of the
outputs
Default output status channel x
(x = 0 ... 7)
WAGO-I/O-SYSTEM 750
PROFINET IO
Configuration and Parameter Setting of the Modules
Value
locked*)
released
according to the device settings*)
Outputs are set to 0
Outputs maintain the last valid
value
outputs take on their default value
*)
0
1
*) Default settings
I/O Modules
Significance
With external faults, channel diagnostics and the
respective alarms are
not transferred to the I/O controller
transferred to the I/O controller
Applies when the I/O controller does not supply
valid output data for the module or the group of
modules
the set strategy on the side of the station
distributor applies (I/O device).
so that all outputs are immediately reset
that all outputs maintain the last valid value
so that all outputs switch to their configured
default value
With the respective configuration of the default value
behavior on the side of the I/O module, these values
are released to binary signal channels with invalid
output station of the I/O controller.
• 185