Detail diagnostics "F Input channels PROFIsafe" (Data set 36, 2 Byte long)
Fault
0x0K01 Cross connection between two input channels that are supplied from two
0x0K27 Discrepancy fault with 2 channel evaluation. K contains the input channel
Detail diagnostics "F Output channels PROFIsafe" (Data set 44, 2 Byte long)
Fault
0x0K04 Overload to output channel K.
0x0K06 Wire break on output channel K.
0x0K23 Short circuit after 24V of the output channel K.
0x0K24 Short circuit after 0V of the output channel K.
Detail diagnostics "F Module PROFIsafe" (Data set 52, 2 Byte long)
Fault
0x0002 Undervoltage field supply
0x0005 Excessive temperature within the PROFIsafe I/O module
0x0009 Fault
0x0019 Safety relevant fault, a hardware fault has occurred on safety relevant
0x0020 External fault, there is a fault in the detail diagnostics for the input or
WAGO-I/O-SYSTEM 750
PROFINET IO
Acyclic Communication using Record Data Sets
Description
different clock signal sources. K contains the number of the input channel
that does not receive a clock signal because of the cross connection. If
there is a cross connection between two independent clock signal sources,
K is written to the input channel that had recognized the fault at first.
that has determined the discrepancy fault.
Description
Description
switching parts or there is a program sequence fault caused by the device
software.
output periphery.
PROFINET IO 750-340
• 95