WAGO -I/O-SYSTEM 750 Technical Description, Installation And Configuration page 17

Profinet io modular i/o-system fieldbus coupler
Hide thumbs Also See for WAGO-I/O-SYSTEM 750:
Table of Contents

Advertisement

Safe electrical isolation
Air and creepage distance
Degree of pollution
acc. To IEC 61131-2
Degree of protection
Degree of protection
Electromagnetic compatibility
Immunity to interference for industrial areas acc. to EN 61000-6-2 (2001)
Test specification
EN 61000-4-2 ESD
EN 61000-4-3
electromagnetic fields
EN 61000-4-4 burst
EN 61000-4-5 surge
EN 61000-4-6
RF disturbances
Emission of interference for industrial areas acc. to EN 61000-6-4 (2001)
Test specification
EN 55011 (AC supply,
conducted)
EN 55011 (radiated)
Emission of interference for residential areas acc. to EN 61000-6-3 (2001)
Test specification
EN 55022 (AC supply,
conducted)
EN 55022 (DC supply/data,
conducted)
EN 55022 (radiated)
WAGO-I/O-SYSTEM 750
PROFINET IO
Technical Condition of the Devices
acc. to IEC 60664-1
2
IP 20
Test values
4 kV/8 kV (contact/air)
10 V/m 80 MHz ... 1 GHz
1 kV/2 kV (data/supply)
Data:
-/- (line/line)
1 kV (line/earth)
DC
0.5 kV (line/line)
supply:
0.5 kV (line/earth)
AC
1 kV (line/line)
supply:
2 kV (line/earth)
10 V/m 80 % AM (0.15 ... 80
MHz)
Limit values/[QP]*) Frequency range
79 dB (µV)
73 dB (µV)
40 dB (µV/m)
47 dB (µV/m)
Limit values/[QP]*) Frequency range
66 ... 56 dB (µV)
56 dB (µV)
60 dB (µV)
40 ... 30 dB (µA)
30 dB (µA)
30 dB (µV/m)
37 dB (µV/m)
Technical Data
Strength
Evaluation
class
criteria
2/3
B
3
A
2/3
B
B
2
1
B
1
2
B
3
3
A
150 kHz ... 500 kHz
500 kHz ... 30 MHz
30 MHz ... 230 MHz
230 MHz ... 1 GHz
150 kHz ... 500 kHz
500 kHz ... 5 MHz
5 MHz ... 30 MHz
150 kHz ... 500 kHz
500 kHz ... 30 MHz
30 MHz ... 230 MHz
230 MHz ... 1 GHz
• 9
Distance
10 m
10 m
Distance
10 m
10 m

Hide quick links: