214 • I/O Modules
Configuration and Parameter Setting of the Modules
F-Parameter
F_Check_iPar
F_SIL
F_CRC_Length
F_Par_Version
F_Source_Add
F_Dest_Add
F_WD_Time
Value
1)
NoCheck
Check
1)
SIL3
1)
3-Byte-CRC
1)
1
1 ...65534
1 ...1022
*)
50 ... 100
... 10000
*) Default settings
1)
settings that cannot be modified
Significance
Manufacturer specific i-parameters can be found
within the F-parameters that
not requested for inspection
requested for inspection
The safety catagory reached is
SIL 3
The length of the CRC for backing up the process
data is
3 Byte
The version of the F Parameter set is
1 = V2-Mode
PROFIsafe address of the F-Host
PROFIsafe address of the I/O module (F-Slave)
Monitoring time of the F Data set in ms