Parameter
Default value behavior of the
outputs
Asynchronous diagnostics
message
Channel x (x = 0 ... 3)
Process data format channel x
(x = 0 ... 3)
Substitute output data channel x
(x = 0 ... 3)
WAGO-I/O-SYSTEM 750
PROFINET IO
Configuration and Parameter Setting of the Modules
Value
according to the device settings*)
Outputs are set to 0
Outputs maintain the last valid value
outputs take on their default value
locked*)
released
according to the device settings*)
INTEL (LSB-MSB)
MOTOROLA (MSB-LSB)
*)
0x0000
– 0x7FFF
or
*)
0x0000
– 0xFFFF
*) Default settings
I/O Modules
Significance
Applies when the I/O controller does not supply
valid output data for the module or the group of
modules
•
the set strategy on the side of the station
distributor applies (I/O device).
•
so that all outputs are immediately reset
•
that all outputs maintain the last valid value
•
so that all outputs switch to their configured
default value
The following occurs per diagnostics data sets and
diagnostics alarm with external faults
•
not transferred to the I/O Controller
•
transferred to the I/O Controller
The process data will be transferred
•
using the format settings of the I/O device.
•
Little Endian Format
•
Big Endian Format
If the switching of substitute values has been
selected as a fault strategy, the substitute output
data of the individual output channels can be
determined here.
• 201