Difference Between Target And Actual Configuration - WAGO -I/O-SYSTEM 750 Technical Description, Installation And Configuration

Profinet io modular i/o-system fieldbus coupler
Hide thumbs Also See for WAGO-I/O-SYSTEM 750:
Table of Contents

Advertisement

92 •
PROFINET IO 750-340
Diagnostics
3.1.7.2.3

Difference between Target and Actual Configuration

A diagnostics is performed by the coupler when there is a difference between
the module configuration of the I/O controller and the number of connected
sub-modules (I/O modules).
The BlockType in the head structure of the data set corresponds to the
value of the module differences (0x8104). The length gives information on the
differences between the configured and connected modules or sub-modules.
A structure head is used for the module differences.
Byte
offset
0 / 1
2 / 3
4 / 5
The number of data sets for each module that has been faulty configured is
stored in the head structure.
Byte
offset
14 / 15
16 / 17
10 / 11
12 / 13
14 / 15
The data sets of faulty configured sub-modules are following the data set of
one module.
Data type
0x00
0x00
DWORD
0x00
0x00
WORD
Data type
WORD
DWORD
WORD
WORD
Description
API (Application Process Instance) = 0
Number of slots with differences between target and actual
configuration
dependent on the number of data sets that follow
Description
Module slot with set / actual deviation
1 ... 255
Value range
Identification of the physically connected modules
Module status
0x0000 no module is connected
0x0001 Physically connected and configured module do not
correspond
0x0002 Physically connected and configured module correspond
but at least one sub-module is missing or does not
correspond.
0x0003 Physically connected and configured module do not
correspond but are compatible
0x0004
...
reserved
0xFFFF
Number of sub-module slots where a difference between the target and
actual configuration exists, otherwise 0
WAGO-I/O-SYSTEM 750