1: Setting An Slc Address For A Single Point Module - Honeywell SLC Installation Manual

Intelligent control panel
Table of Contents

Advertisement

Monitor Modules
5.2.1 Setting an SLC address for a Single Point Module
Each module can be set to one of 159 addresses (01-159) and is factory preset with an address of
"00".
NOTE: The MS-9050UD can support addresses 01 - 50. The MS-9200, MS-9200UD, and MS-
9200UDLS can support module addresses of 01 - 99. The MS-9600, MS-9600LS, and MS-
9600UDLS can support module addresses 01 - 159. The plastic stop located on the Tens switch
must be removed to set addresses above 99.
To set an SLC address, use a screwdriver to adjust the rotary switches on the module to the desired
address. The module below is set at "35". When finished, mark the address on the module face in
the place provided.
Modules with
Rotary Switches
in vertical
position
34
6 7
8 9
6 7
8 9
10
5
5
11
4
4
12
3
3
13
2
2
1
14
1
0
15
0
ONES
TENS
Modules with Rotary
Switches in
horizontal position
Dual monitor modules: On dual monitor modules, only even
numbers appear on the ONES rotary switch. The module takes
both the selected address and the next-higher address.
Figure 5.7 Setting an SLC Address on a Single Point Module
Breakaway Tab - Modules come with
a raised breakaway tab on the TENS
rotary switch. This tab must be
removed when the module is on an
FACP that uses more than 99
addresses.
FireLite SLC Wiring Manual — P/N 51309:P4 9/17/2014