DO820
Default value is 0.
DQ CYCLE TIME
Enter the channel data quality update period (msec) over the fieldbus. Refer to the
S800 I/O User's Guide for details of AF 100 loading in relation to cycle time.
The valid values are:
1, 2, 4, 8, 16, 32, 64, 128, 256, 512, 1024, 2048, and 4096
The default value is 128.
LABEL
Enter a characteristic name to identify the DO820 Module of the station. The name
may contain up to 20 characters.
MONITOR POWER
To monitor process power source enter a YES;
if not needed enter a NO.
Default Value is NO.
OSP HOLD 01 through 08
If an OSP TIMEOUT has occurred, will the DO820 hold the last value during OSP?
Enter a YES if it will, or enter a NO if an OSP VALUE will be used.
The Default is NO.
OSP TIMEOUT
Enter the time (msec) after communications is lost, that outputs go to OSP value.
The valid values are:
OFF, 256, 512, and 1024.
The default value is 1024.
316
Appendix A Runtime Templates
3BUR002418-600 A