Appendix A Runtime Templates
ATTRIBUTE NAME Field
This field specifies the mnemonic of the source parameter. An entry must be made
to this field. Valid entry is a parameter mnemonic.
DATAQUAL ATTRIBUTE Field
This field specifies the parameter from which to obtain the data quality of the
parameter named in the ATTRIBUTE NAME field. When this parameter is obtained
it is stored in the data quality of the result parameter (DATAQUAL). Valid entry is a
parameter mnemonic.
ALARM CONDITION Field
This field is used to get the current status of an alarm for the parameter named in the
ATTRIBUTE NAME field. This field specifies the type of alarm to check. It must be
appropriate for the entry in the ATTRIBUTE NAME field. For example, the SETPT
HI entry for this field should only be used when the entry in the ATTRIBUTE
NAME field is a setpoint. You can check only one alarm for a variable. The alarm
status becomes the result of the Get FCM. Valid entries are:
3BUR002418-600 A
NONE
do not obtain an alarm state
DQ BAD
measured variable bad data quality alarm
HIHI
measured variable high high alarm
HI
measured variable high alarm
LO
measured variable low alarm
LOLO
measured variable low low alarm
IROC HI
measured variable input rate of change alarm
OUT DQ B output bad data quality alarm
OUT HI
output high alarm
OUT LO
output low alarm
OUT IRC
output rate of change alarm
SETPT DQ setpoint bad data quality alarm