Single Loop Operation in Automatic Mode

Single Loop Operation in Automatic Mode
Typical operations for a single control loop in the automatic mode can be with local
setpoint, remote setpoint, and remote setpoint with ratio and bias.

Single Loop Automatic Operation with Local Setpoint

When a control loop is configured for single loop operation with local setpoint, the
faceplate displays and control button operations resemble the example below.
196
indicates that the controller is in automatic
mode. Current output value cannot be
changed in automatic.
indicates local setpoint is active. Shaded
setpoint value field and slide bar on setpoint
graphic indicates that the local setpoint can
be changed in automatic. Use the slider or the entry
value box [Sp] to change the value with confirmation.
An engineering units label has been configured for
degrees Centigrade (DEGC).
Use the remote button to switch from local to
remote.
Use the manual button to switch from
automatic to manual. Output can be changed
in the manual.
Section 8 Operation Examples
3BUR002418-600 A