DI820
The default value is YES.
AUTO DOWNLOAD
To automatically download the configuration to the I/O module enter a YES. In the
future, if the configuration is to be loaded locally enter a NO.
Default value is YES.
CLUSTER
Enter the I/O device cluster of the station where this module is located. The cluster
connected directly to the FCI is number zero (0). The number in this field is 0 -7.
Default value is 0.
FILTER
Enter the input filter time in msec.
The valid values are:
2, 4, 8 and 16.
The default value is 2.
LABEL
Enter a characteristic name to identify the DI820 Module of the station. The name
may contain up to 20 characters.
MONITOR POWER
To monitor process power source enter a YES;
if not needed enter a NO.
Default Value is NO.
POSITION
Enter a number from 1 to 12 representing the position of the I/O module relative to
the FCI. The I/O module directly next to the FCI is number 1.
306
Appendix A Runtime Templates
3BUR002418-600 A