Appendix A Runtime Templates
PT100, that will be connected to channel 8. The type LINEAR is used if the input is
a -25mV to 75mV signal.
The valid values are:
B, C, E, J, K, N, R, S, T, PT100 and LINEAR
The default entry is J.
TEMPERATURE UNIT
Enter the temperature's unit of measure; either Centigrade or Fahrenheit.
The valid values are:
C and F
The default value is C.
VALUE CYCLE TIME
Enter the channel value update period (msec) over the fieldbus. Refer to the S800
I/O User's Guide for details of AF 100 loading in relation to cycle time.
The valid values are:
1, 2, 4, 8, 16, 32, 64, 128, 256, 512, 1024, 2048 and 4096.
The default value is 128.

AO810, AO890

The S800 I/O AO810 Analog Output Module templet is also used for the AO890
except as noted in the field entry descriptions.
ACTIVE 01 through 08
If the channel is to be active enter a YES. If the channel will not be used enter a NO.
The default value is YES.
AUTO DOWNLOAD
To automatically download the configuration to the I/O module enter a YES. In the
future, if the configuration is to be loaded locally enter a NO.
3BUR002418-600 A
AO810, AO890
295