AI835

VALUE CYCLE TIME
Enter the channel value update period (msec) over the fieldbus. Refer to the S800
I/O User's Guide for details of AF 100 loading in relation to cycle time.
The valid values are:
1, 2, 4, 8, 16, 32, 64, 128, 256, 512, 1024, 2048 and 4096.
The default value is 128.
AI835
S800 I/O AI835
ACTIVE 01 through 08
If the channel is to be active enter a YES.
If the channel will not be used enter a NO.
The default value is YES.
AUTO DOWNLOAD
To automatically download the configuration to the I/O module enter a YES. In the
future, if the configuration is to be loaded locally enter a NO.
Default value is YES.
CLUSTER
Enter the I/O device cluster of the station where this module is located. The cluster
connected directly to the FCI is number zero (0). The number in this field is 0 -7.
Default value is 0.
DEAD BAND 01 through 08
Enter the difference in successive signal count values before a new value will be
sent.
The valid values are:
NONE, 0, 1, 3, 7, 15, 31, 63, 127, 255, 511, 1023, 2047, 4095, 8191 and 16383.
292
Thermocouple Input Module Templet.
Appendix A Runtime Templates
3BUR002418-600 A