Appendix A Runtime Templates
field. If you want the specified abnormal override actions to occur, you must enter a
non-zero entry. Abnormal state change alarms will occur (if the device is so
configured), regardless of the entry in this field.
Valid entry is an amount of time in whole seconds.
SECONDARY TIMER Field
This field is used when the device loop uses a user-defined TCL device handling
algorithm. It sets the initial time for a countdown timer used by the TCL program
which sets up the user-defined device algorithm.
Valid entry is an amount of time in whole seconds.
TIMER Field
This field sets the time for the device loop's feedback timer. When the loop sends a
command to the device, the feedback timer starts counting down. The loop starts
checking its input to see if the device has gone to the desired state. A timeout alarm
is generated if the device has not entered the desired state by the time the timer
expires.
Valid entry is an amount of time in whole seconds.
DEV INTERLOCK ENABLE Field
This field specifies whether the device interlock is enabled or disabled. When it is
enabled, the result of the FCM named in the DEV INTERLOCK SOURCE field
determines whether the device is locked. When the result goes true the device is
locked and the only possible command entry is the one specified in the
PERMITTED COMMAND field.
Valid entries are:
YES
NO
3BUR002418-600 A
enable the interlock
disable the interlock
Device Loop Templet