AI835
The default entry is 0 (zero)
LABEL
Enter a characteristic name to identify the AI835 Module of the station. The name
may contain up to 20 characters.
POSITION
Enter a number from 1 to 12 representing the position of the I/O module relative to
the FCI. The I/O module directly next to the FCI is number 1.
Default value is 1.
If positions are to be used for spare MTUs, the spares must be in place so the rest
of the I/O modules are numbered correctly. The spare MTU will use a position
number when it is on the ModuleBus.
POWER LINE FREQUENCY
Enter the power line frequency to filter out (notch) the signal.
The valid values are:
16, 50, and 60.
The default value is 60.
REPORT FAULTS 01 through 08
If channel faults are to be reported, enter a YES; if not enter a NO.
The default value is YES.
RESERVED OPTIONS
This field reserved for future use. A zero (0) should be entered as a default value.
TC TYPE 01 through 08
Enter the type of sensor that will be connected to each channel. When channel 08
serves as the Cold Junction Compensation value, enter the sensor type, normally