S100 I/O Displays; S100 Lan Display - ABB 800xA Operation

For mod 300
Hide thumbs Also See for 800xA:
Table of Contents

Advertisement

Section 7 I/O Displays
For continuous loops with Analog and Digital Output FCMs or device loops
configured for warmstart that have been warm started, the tag is shown with a
white background.
When CCF loops with output FCMs configured for warmstart are placed in the
MANUAL mode by either a warmstart or user action, their tags are shown with a
white background. When device loops configured for warmstart have their
DEV_CMND parameter set to NO COMMAND by either a warmstart action or
TCL command, their tags are also shown with a white background. Note that the
loop warm started for a given channel is the loop whose tag is shown in the S800
I/O Display. If two or more loops reference the same channel, only the last loop
downloaded participates in warmstart and is listed on the S800 I/O Display.

S100 I/O Displays

These S100 runtime displays relate to the Series 100 process interface as described
in the S100 I/O User's Guide where you can find additional information about S100
I/O.

S100 LAN Display

The S100 LAN display,
about each S100 device configured under a particular LAN. Display links for each
device are located in the first five columns of the row for the device. If a redundant
device is configured, the display link for the redundant device is activated in the last
two columns for the device row. Select the device display link to call up the S100
I/O Device Status display for that device.
3BUR002418-600 A
Figure
71, shows the submodule status and information
S100 I/O Displays