S100 LAN Display
Figure 71. S100 LAN Display
The heading fields on the S100 LAN display are described below.
Devsub
State
Name
Lan
Mod/
Sub
162
The controller DCN address where the S100 I/O is located.
The runtime status of the controller. ACTIVE indicates the
submodule is in use. FAILED means the submodule has stopped.
The controller part of the logical controller name created during
database configuration is given in this field.
This field represents the number (1 to 4) of the local area network
for all the primary I/O boards listed below.
For the AC 460 controller, this field represents the position of the
SC510 in the Futurebus+ backplane (3, 4, 7, 8, 11, 12).
For the AC 410 controller, it represents the position of PM150 in
the 410 controller. This is always = 1.
For the AC 460 controller this field corresponds to where the S100
interface is attached to the I/O submodule (CI540) on the front of
the SC510 card (1 = top, 2 = bottom).
For the AC 410 controller it corresponding to the 5th interface
(S100 integrated backplane) on the 410 controller.