Printing Displays

Printing Displays
To print the active window of a display, use the Print Screen key to capture the
screen, paste the image into an application such as Microsoft Word and then send it
to the printer. For best resolution, maximize detail displays to full screen before
printing.
By default, the MOD Environment Group Trend, Group Status, Group Graphic and
Area Status print in the landscape mode for best orientation.

Alarm/Event Handling

When rebooting a Connectivity Server node pair where MOD 300
messages/events are routed, wait until the primary Connectivity Server node is
fully booted and active before rebooting the standby Connectivity Server node to
prevent an alarm mismatch.
MOD 300 has multiple alarm conditions per object (Measure, Setpoint, Output,
Deviation and so forth). To handle these properties, a MOD Alarm/Event List is
provided as an aspect. Alarm/Events are handled as follows.
Alarm/Event types with user action (acknowledgement):
Event types with no user action required (for history/loggers only):
30
CCF (Measure, Setpoint, Output, Deviation, Device).
TCL (Message, Reply, Error, Unit Alarm).
Diagnostics.
User Ack (outgoing).
TCL Reply (outgoing).
Global Ack broadcast (incoming).
Global Ack broadcast (outgoing).
Parameter Change (incoming) - NOTE: Parameter change messages for
template and faceplate changes always come through as Administrator.
User Log On/Off (incoming).
User Ack (incoming).