Appendix A Runtime Templates
Input FCMs
This section describes the active runtime fields on the input FCM templets.
Common Fields
INITIAL OUTPUT MODE Field
This field determines the output mode for the FCM at startup. Valid entries are:
INITIAL OUTPUT Field
This field determines the result (output value of the FCM) in effect upon startup of
the FCM. Valid entry is a decimal number.
Analog Input FCM
COUNTS - LOWER BOUND Field
This field specifies the lower limit for the range of counts. It corresponds to the
engineering units lower bound. Valid entry is an integer between 0 and 32767.
COUNTS - UPPER BOUND Field
This field specifies the upper limit for the range of raw counts. It corresponds to the
engineering units upper bound. Valid entry is an integer between 0 and 32767.
ENGU - LOWER BOUND Field
This field specifies the engineering units range lower limit. Valid entry is a decimal
number.
3BUR002418-600 A
AUTO
FCM determines output values
MAN
operator determines output values