Time Integration FCM

The Time Integration FCM performs time integration on its input. The calculation is
a trapezoidal approximation of the integral.
SCALE FACTOR Field
This field specifies the value of the scaling constant. Valid entry is any number.

First Order Filter FCM

The First Order Filter FCM provides a first order lag function.
LAG TIME Field
This field specifies the value of the lag time. Valid entry is an amount of time in
minutes.

Totalizer FCM

The Totalizer FCM calculates a total by adding or subtracting its current input from
the total of the previous input values. You can also compare the total to two user-
defined values.
SCALE FACTOR Field
This field specifies the value of the scaling constant. Valid entry is any number.
TRIP POINT 1 Field
This field specifies the value of PREDETERMINED REGISTER NO. 1. Valid entry
is any number greater than or equal to 0.
TRIP POINT 2 Field
This field specifies the value of the PREDETERMINED REGISTER NO. 2. Valid
entry is a number greater than or equal to the TRIP POINT 1 entry.