S800 Station Display
FCI - X Status Area
FCI Status areas represent a CI810A FCI or the redundant CI820 FCIs. For the
CI810A, the status box contains the current state of FCI - 1. For the redundant
CI820 FCIs, the left status box contains the current state of FCI - 1 (or the left FCI),
the right status box contains the current state of FCI - 2 (or the right FCI).
State
FCI - X Menu
Each FCI - x status area contains a FCI button. Select the FCI button to display the
menu items described below.
State
RPT Faults
Get
Diagnostics
154
This field shows the status of the FCI (CI810A/CI820).
ACTIVE indicates the FCI is in use.
BACKUP indicates the station is running redundantly and the
backup is available.
READY indicates a transient state on the way to becoming
ACTIVE or BACKUP.
FAILED means the FCI has stopped.
MISSING means there is not an FCI connected.
UNKNOWN is an indeterminate state, sometimes seen as a
transient state as the station changes state.
User can change state to:
RESTART re-initializes the lan,
DEACTIVATE forces all data qualities to 'bad',
ACTIVATE sets data qualities based on the active status.
SWITCHOVER switches to a backup interface if present.
Switchover is not used for non-redundant FCIs.
User can select to change reporting method to: Flash Notify, Silent
Notify or No Notify.
Select this to get the diagnostics dialog.
Section 7 I/O Displays
3BUR002418-600 A