S100 Device Status Display - ABB 800xA Operation

For mod 300
Hide thumbs Also See for 800xA:
Table of Contents

Advertisement

Section 7 I/O Displays
The column headings for each device row on the S100 I/O overview display are
described below.
Device
Templet
Dev Type
Comm Addr
Dev State
Red Dev
Red State

S100 Device Status Display

The S100 Device Status Display,
each channel configured for the S100 I/O board (device diagnostics are not
displayed). Use the context menu to move up to the LAN display.
3BUR002418-600 A
This field is the logical block number of the S100 device as
specified during database configuration.
The logical device name created during database configuration is
given in this field.
This field shows the specific I/O board type.
This field is the hexadecimal communication address assigned
during database configuration.
This field shows the runtime status of the I/O board. ACTIVE
indicates the primary I/O board is in use, processing I/O signals.
FAILED means the primary I/O board has stopped handling I/O
signals and the redundant I/O board may be ACTIVE if configured.
UNKNOWN indicates not installed.
If the I/O board has a redundant partner configured, the address
of the redundant board is given. The format (LL DD) indicates the
lan and device of the redundant I/O board. Click on the redundant
device to get the S100 I/O Device Status display. If a redundant
board is not configured, '00 00' is displayed.
The status of the redundant I/O board. 'Ready' means the
redundant I/O board is available to backup the primary I/O board.
ACTIVE indicates the redundant I/O board is in use, backing up
the primary I/O board. If a redundant I/O board is not configured,
this field will show NOT CONFIG. The DSAX 110 can show that
both the primary and backup boards are ACTIVE since both
boards drive the outputs at 50% of required value.
Figure
S100 Device Status Display
72, shows information for the device and
163