AI820
The default is NO.
POSITION
Enter a number from 1 to 12 representing the position of the I/O module relative to
the FCI. The I/O module directly next to the FCI is number 1.
Default value is 1.
If positions are to be used for spare MTUs, the spares must be in place so the rest
of the I/O modules are numbered correctly. The spare MTU will use a position
number when it is on the ModuleBus.
POWER LINE FREQUENCY
Enter the power line frequency to filter out (notch) the signal.
The valid values are:
16, 50, and 60.
The default value is 60.
RANGE 01 through 04
The valid values are:
-10..10V
-20..20mA
-5..5V
The default range is -20..20mA.
REPORT FAULTS 01 through 04
If channel faults are to be reported, enter a YES; if not enter a NO.
The default value is YES.
RESERVED OPTIONS
This field reserved for future use. A zero (0) should be entered as a default value.
288
Appendix A Runtime Templates
3BUR002418-600 A